碧波液压网 欢迎你,游客。 登录 注册

PT二次回路防止误接线方法研究

版权信息:站内文章仅供学习与参考,如触及到您的版权信息,请与本站联系。

  

  

  Abstract:Themethod of prohibitwrongwiring for the PT secondary circuitwas simply introduced. Themain parameter influen-tial factors in selecting the accuracy, nomoralwiringmethod of secondarywindingswere analyzed in firstly. And things to be no-ticed were brought forwardwhen voltage transformerwas ploughed into operation andwas operating secongly. Finally, two practi-calmethodswas offered based on two sides before and afterwiring to effectively classifywhether secondary circuitwiringwas cor-rect. The research results show that themethods illustrate a good prospect of application and extension.

  Key words:potential transformer(PT); wiringmode; secondary circuit

  0 引 言

  电压互感器(PT)是变换电压的电气设备,它的主要作用是:对低电压的二次系统与高电压的一次系统实施电气隔离,以保证工作人员安全;将一次回路的高电压变成二次回路的标准值,供测量仪表和继电器使用;取得零序电压分量与从电流互感器取得的零序电流分量配合供反应接地故障的继电保护装置使用。由此可以看出,PT二次接线正确与否直接决定其能否真正反映一次系统的工作状况,从而影响电网的安全稳定运行。本研究主要探讨PT二次回路防止误接线方法。

  1 接线前的准备

  1.1 电压互感器的主要参数

  (1)准确等级。

  按照《测量用电压互感器检定规程》,PT的准确度等级可分为:0.001、0. 002、0. 005、0. 01、0. 02、0. 05、0.1、0.2、0.5、1共10级。互感器的误差包括比值差和相位差,每一个准确等级的互感器都对此有明确的要求。

  (2)额定电压比。

  额定一次电压与额定二次电压的比例:

  PT额定电压比与匝数比成正比,即与一次匝数成正比,与二次匝数成反比。

  (3)额定一次电压。

  PT额定的输入一次回路电压U1n。电力系统常用互感器的额定一次电压为: 6 kV, 6/1. 732 kV, 10 kV,10/1. 732 kV, 35 kV, 35/1. 732 kV, 110/1. 732 kV,220/1. 732 kV, 500/1. 732 kV等,其中1/1. 732 kV的额定电压值用于三相四线制中性点接地线路的单相互感器。

  (4)额定二次电压。

  PT的额定输出二次回路电压U2n。电力系统常用二次电压为: 100 V, 100/1. 732 V。接于三相四线制中性点接地线路的单相互感器,其二次电压额定电压应为100/1. 732 V。

  (5)额定二次负荷。

  互感器在额定电压和额定负荷下运行时二次所输出的视在功率,额定输出的标准值为10、15、25、30、50、75、100、150、200、250、300、400、500 VA。对三相互感器而言,其额定输出是指每相的额定输出。

  1.2 接线方式

  PT最常见的接线方式有如下几种:①1只单相电压互感器用来测量相间电压;②用2只单相电压互感器接成不完全星形(V,V)接线,广泛应用于中性点不接地或经消弧线圈接地的电网中;③3只单相电压互感器或三相五柱式电压互感器接成Y, yn接线,另外还可接成YN, yn接线。